6ES7417-4HT14-0AB0 6ES7-417-4HT14-0AB0 SIMATIC S7-400H, CPU 417H CENTRAL UNIT

6ES7417-4HT14-0AB0 6ES7-417-4HT14-0AB0 SIMATIC S7-400H, CPU 417H CENTRAL UNIT

S7-400 PRODUCTS Parameter SIMATIC S7-400H, CPU 417H CENTRAL UNIT FOR S7-400H 4 INTERFACES: 1 MPI/DP, 1 DP A. 2 FOR SYNC MODULES 30 MB MEMORY (15 MB CODE/15 MB DATA) More S7-400 Order NO. and version: 6ES7417-4HT14-0AB0 B 6ES7417-4HT14-0AB0 D

 

Siemens S7-400 ,H6ES7417-4HT14-0AB0CPU 417H, 4 SS, 30MB, F. S7-400H/F/FH

General information
Hardware product version 1
Firmware version V4.5
Engineering with
● Programming package STEP 7 V5.3 SP2 or higher with HW update
CiR – Configuration in RUN
CiR synchronization time, basic load 60 ms
CiR synchronization time, time per I/O byte 10 µs
Supply voltage
Rated value (DC)
● 24 V DC No; Power supply via system power supply
Input current
from backplane bus 5 V DC, typ. 1.5 A
from backplane bus 5 V DC, max. 1.8 A
from backplane bus 24 V DC, max. 150 mA; Per DP interface
from interface 5 V DC, max. 90 mA; At each DP interface
Power loss
Power loss, typ. 6.5 W
Memory
Type of memory other
Work memory
● integrated 30 Mbyte
● integrated (for program) 15 Mbyte
● integrated (for data) 15 Mbyte
● expandable No
Load memory
● expandable FEPROM Yes
● expandable FEPROM, max. 64 Mbyte
● integrated RAM, max. 256 kbyte
● expandable RAM Yes
● expandable RAM, max. 64 Mbyte
Backup
● present Yes
● with battery Yes; all data
● without battery No
Battery
Backup battery
● Backup current, typ. 970 µA; Valid up to 40°C
● Backup current, max. 1 980 µA
● Backup time, max. Dealt with in the module data manual with the secondary conditions and the factors of influence
● Feeding of external backup voltage to CPU 5 V DC to 15 V DC
CPU processing times
for bit operations, typ. 0.018 µs
for word operations, typ. 0.018 µs
for fixed point arithmetic, typ. 0.018 µs
for floating point arithmetic, typ. 0.054 µs
CPU-blocks
DB
● Number, max. 8 191; Number range: 1 – 8191
● Size, max. 64 kbyte
FB
● Number, max. 6 144; Number range: 0 – 6143
● Size, max. 64 kbyte
FC
● Number, max. 6 144; Number range: 0 – 6143
● Size, max. 64 kbyte
OB
● Size, max. 64 kbyte
● Number of time alarm OBs 8
● Number of delay alarm OBs 4
● Number of cyclic interrupt OBs 9
● Number of process alarm OBs 8
Nesting depth
● per priority class 24
● additional within an error OB 2
Counters, timers and their retentivity